Boiler simulation (safety drill) the purpose of the safety drill is to check whether the safety equipment on the boiler can work properly. S...
Daftar Isi [Tampil]



    Boiler simulation (safety drill)

    the purpose of the safety drill is to check whether the safety equipment on the boiler can work properly. Safety drills are usually done once a week.

    We need to check:

    1. Boiler alarm for high, low and low-low level.

    2. Check the mobrey control when the water level is raised, it opens and closes when it is lowered

    3. IDF / FDF / SA / Fiber Jet Fan conditions

    4. Check the furnace draft fan

    5. Interlock boiler



    Step by Step Safety Drill

    1. Test Alarm

    Fill the boiler at normal water level. Increase water level to high water level Check whether the alarm / siren sounds or not, lower the water level to low level and test the alarm / siren sounds or not.


    2. Test Mobrey Control

    Check the mobrey control when the water level is high and low, whether the mobrey can open and close properly.


    3. Induced Draft Fan, Forced Draft Fan, Secondary Draft Fan and Fiber Jet Fan

    Check the induced draft fan, forced draft fan, secondary draft fan and fiber jet fan whether they are in good condition and can work properly. Check the amperage and record it and compare it with the normal operating amperage. Also check if there are vibrations that are excessive than usual.

    It should also be noted that the ampere condition of the IDF fan when the flue gas is cold and hot, there will be a difference.


    4. Furnace Draft Fan

    Check the furnace draft whether the vacuum in the furnace matches the vacuum recommended by the manufacturer


    5. Interlock System

    Turn on the induced draft fan, forced draft fan, secondary draft fan, fiber jet fan and feed water pump. Pump water at normal level. Raise the water level to a high level. Notice if the alarm sounds and the electric water pump stops. Lower the water level slowly again until it reaches low water level. Check if the alarm sounds and the electric feed water pump continues.


    Lower the water until it reaches low-low level. Check whether the interlock on the boiler can work properly.

    - Induced draft fan stop

    - Forced draft fan stop

    - Secondary draft fan stop

    - Fibre jet fan stop

    - The pump keeps running.